LORAIN Industrial Partner

A50B50 - MODULAR 50A RECTIFIER Simple Type: Rectifier

larger image

Request Quote
For Price
Part Number:
A50B50
Model Number:
A50B50
Make:
LORAIN
Lead Time:
Available
Qty In Stock:
Available

MODULAR 50A RECTIFIER Simple Type: Rectifier

The NetSure A50B50 DC Power Retrofit provides a unique solution for maintaining and upgrading legacy Lorain DC power systems based on the A50B50 rectifier. Specially designed frames mount directly into existing rectifier slots without the need for electrical or mechanical adjustments. These frames accommodate the R48-3500E and R48-3200E eSure high efficiency rectifiers as well as the standard R48-3200 cool rectifier. Two distinct frames are available. Model A50IFRM accommodates a single rectifier and controller. Model A50EFRM houses a single rectifier. Each system does starts with one A50IFRM. The A50EFRM provides growth for up to thirty-six rectifiers in a single system. The NetSure A50B50 DC Power Retrofit can be used with or without the original A50B50 rectifiers in the same system. The frames contain the necessary connections and nice circuitry to manage the monitoring and alarming of all rectifiers. The system’s original meter-control-alarm panel can remain in place. Or, if desired, the NetSure controller can be used instead, providing significant enhancements over existing electronics including programmable alarming, customer I/O and local/remote access over Ethernet.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • Constant power limiting feature increases current capacity to 73 amps per rectifier
  • Enhanced controller features including single point adjustment and remote access via Ethernet
  • Increases efficiency from 85%to >96%; reduces energy consumption by >11%; reduces heat loss by >73%
  • NetSure reliability improves mean time between failure (MTBF)
  • Operates with or without original A50B50 rectifiers in same system
  • Plugs right into A50B50 rectifier slot without any electrical or mechanical adjustments to existing shelf or system

Specifications

    General
  • AC input: R48-3200 R48-3200e R48-3500e
  • Altitude: Up to 6562 ft (2000m) at full rated output
  • Audible noise: The rectifier does not produce sound levels above 53dB(A), measured 0.6m in front of the rectifier, at the same horizontal lines the middle of the rectifier at 25°C.
  • Compliance: UL recognized (UL 60950) for USA & Canada, CE marked, EN 300 386:2001 class B, FCC part 15 class B, IEC 60950, EN 60950
  • Constant power limiting operation: 3200W maximum from 176VAC to 290VAC at 48VDC output 3500W maximum from 176VAC to 290VAC at 48VDC output
  • Current limiting protection: Current limit adjustable from 5 to 67A current limit adjustable from 6 to 73A
  • Dimensions (H x W x D): 5.20 x 3.36 x 11.3 inches (132 x 85.3 x 287mm)
  • Frequency: 45 Hz to 65 Hz
  • High voltage shutdown: If rectifier detects over voltage it will turn off. After 5 seconds it will restart; if it encounters an over voltage within 5 minutes it will
  • Input Current: 16.0A typical, 20.3A maximum 15.2A typical, 19.6A maximum 16.5A typical, and 21.4A maximum
  • Input Protection: If the input voltage decreases or increases beyond a fantastic non-adjustable predetermined value, the rectifier circuitry shuts down,disabling
  • Inrush current: Does not exceed 150% of the rated input steady state peak value.
  • Lorain: A50B50
  • Mounting: Plug-in installation
  • Nominal voltage single phase: 208/240VAC
  • Operating efficiency: 92% peak 96.8% peak 96.7% peak DC Output
  • Operating voltage range: 176VAC to 275VAC
  • Output Current: 67A max 73A max
  • Output voltage range: -42.0VDC to -58.0VDC
  • Over current protection: Internal fuse
  • Power Factor: (PF) >0.98 from 50% to 100% load
  • Psophometric noise: Does not exceed 1 MV, 10% to 100% load Does not exceed 2 MV, 10% to 100% load
  • Regulation: Steady state output voltage remains within +/-0.25% for any combination of input voltage from 5% to 100% load
  • Relative humidity: 0 to 95%
  • Status Settings: The controller establishes all rectifier settings. Reported via CAN bus to system controller.
  • Temperature: -40°F to 113°F (-40°C to 45°C) at full rated output -40°F to +167°F (-40°C to +75°C) with derating
  • Total Harmonic Distortion: =5% from 50% to 100% load
  • Ventilation: Front to back with speed-controlled fan (field replaceable)
  • Visual Indicators: Normal operation/Green LED/alarm/Yellow LED/rectifier failure alarm/ Visual indicators
  • Voice band noise: The voice-frequency noise generated by a rectifier does not exceed 32dBrnC output noise from 10% to 100% load
  • Weight: 7.7 lbs. (3.5kg)
  • Wide band noise: Does not exceed 250 MV peak-to-peak, or 30 MV RMS per Telcordia GR-947-CORE

 

Applications

  • None Available

Aliases

  • None Available